Not an Airefrig customer? Complete our online account application form here to apply for a credit account.

  • TUA / TUAE, Thermostatic expansion valves

    TUA / TUAE stainless steel thermostatic expansion valves are used for liquid injection into evaporators on both refrigeration and air conditioning systems using flourinated refrigerants e.g. R134a, R404A, R407C, R22, R507 and R410A. 

    TUA / TUAE valves are compact in design, light weight and have steel / copper bi-metal connections for fast soldering. They are supplied as parts programme, with separate thermostatic element / valve body, and orifice assembly. 

    TUA has internal equalization, TUAE external equalization. TUA / TUAE are straightway valves, and have adjustable superheat setting.

    Applications:
    • Traditional refrigeration
    • Heat pump systems
    • Air conditioning units
    • Liquid coolers
    • Ice cube machines
    • Transport refrigeration

    Capacity range:
    • 0.11 – 6.56 TR / 0.42 – 23.1 kW

    Benefits:
    • The use of stainless steel makes the valves light and strong
    • Bi-metal connections for safe, fast and convenient soldering
    • Bi-flow function (TUAE: only orifice 1 – 8 )

     

  • Balanced PortNo
    Bi-flowYes (only orifice 1-8)*
    BrandDanfoss
    Capillary Tube Length1.5M
    Danfoss Code Number068U2287
    External Equalised (Yes / No)Yes
    External Equaliser Connection1/4" ODF
    Inlet Connection3/8" ODF Solder
    Interchangeable OrificePurchase Separately
    Maximum Working Pressure34 bar (500 psig)
    Operating Temperature Range-40°C to +10°C
    Outlet Connection1/2" ODF Solder
    RefrigerantR404A / R507
    Supplied with MOPn/a
    TX Valve with Interchangeable Orifice - TypeTUAE
    Valve BodyStraightway

    Notes:

    *TUAE with orifice no.9 can't be used for Biflow operation

  • TX Valve TUAE R404A External Equal -40/+10C 3/8"ODF x 1/2"ODF
  • Danfoss Orifice Selection Chart

     

    See the TUA - TUAE orifice range here.

     