Danfoss Scroll Compressor 3PH R407C R22 PVE Oil Stub Tube - HCP094T4LC6

Danfoss Scroll Compressor 3PH R407C R22 PVE Oil Stub Tube

Part Number: HCP094T4LC6

Danfoss Scroll Compressor 3PH R407C R22 PVE Oil Stub Tube

Part Number: HCP094T4LC6
Danfoss

Sign in to your Aire-Biz account to view pricing and stock levels.

Sign in

Not an Airefrig customer? Complete our online account application form here to apply for a credit account.

  • Danfoss H-Series Scroll Compressors are 100% gas cooled & fitted with an automatic reset line break protector mounted internally on the motor windings. 

    The internal protectors respond to over-current, overheating & are designed to interrupt motor current under a variety of fault conditions such as failure to start, running overload & fan failure etc. 

    If the internal overload protector trips it must cool down to approximately +60 degrees Celsius to reset. (Depending on the ambient temperature this may take up to several hours) 

    Three Phase Sequence & Reverse Rotation Protection 

    The compressor will only operate properly with the correct rotation. If a three phase compressor is wired incorrectly it will run but will have excessive noise, no pressure differential between suction & discharge, plus the suction will become warmer rather than cooler. 

    The smaller range of Danfoss H-Series scroll compressors (up to HLP075) are able to run in reverse rotation safely for up to 150 hours without damaging the compressor, however phase monitors are still recommended. 

    The larger range of Danfoss H-Series scroll compressors (HLP078 onwards) should never be run in reverse. Danfoss recommends phase rotation protection should always be fitted to prevent these compressors from operating in reverse rotation. 

    Single Phase Compressors – Reverse Rotation 

    Brief power interruptions may cause reverse rotation of single phase scroll compressors. The internal protection will stop the compressor & once cooled down will restart with correct rotation. 

    Crankcase heaters are recommended on all stand-alone compressors & split systems. The heater should be energised for a minimum of 12 hours before initial start up (compressor service valves opened) & must remain energised whenever the compressor is off. 

    External High Pressure Switches are required for HCP094,109,120 scroll compressors as these models are not equipped with internal pressure relief valves. 

    Note: Crankcase heater is not supplied with compressor & should be purchased separately if required.

     

  • General Specifications
    Nominal HP8 HP
    Displacement21.9 m³/Hr
    Swept Volume126.02 cm³
    Suction Line ConnectionStub Tube 1-1/8" ODF
    Discharge Line ConnectionStub Tube 7/8" ODF
    Weight44.33 kg
    Oil Charge2.66 L
    Oil TypePVE Oil 320HV
    Electricssquare electrical box with screw terminals
    Electrical Specifications
    Voltage380-415/3/50
    Motor Type3PH
    Max Continuous Current21 amps
    Locked Rotor Amps84 amps
    Rated Load Amps13.5 amps
    Crankcase Heater 170watt, 230volt

    1. Crankcase Heaters are not supplied with compressors & should be purchased separately if required

  • ContactorMC32A240V
    Thermal OverloadMT323K22
    Electronic OverloadGMP403P40A
    Crankcase Heater120Z0059
  • danfoss_scroll_dim_3

    Units Dimensions (mm)
    D184
    H536
    H1369
    H2509
  • R22
    Cond Temp (°C)Evaporating Temperature (°C)
    -15-10-5057.210
    45Capacity (w)10346129731607819615235382541327800
    Input (w)5823578157475716568256635639
    Current (Amps)10.7910.7710.7510.7410.7410.7510.76
    50Capacity (w)9380120251510618578223952420626511
    Input (w)6455637963246284625362416225
    Current (Amps)12.0612.0111.9711.9511.9511.9611.98
    55Capacity (w)108801397417417211652292825171
    Input (w)707769896929689168816869
    Current (Amps)13.5113.4413.413.413.4213.44

    Note:

    Rating Conditions 11.1k Superheat, 8.3K Subcooling
    R407C
    Cond Temp (°C)Evaporating Temperature (°C)
    -15-10-5057.210
    45Capacity (w)9533120011492518349223182432426876
    Input (w)5605558455585519545954195369
    Current (Amps)8.758.778.798.778.658.548.4
    50Capacity (w)8856111971397417233210172293425373
    Input (w)6194617461526120606960345990
    Current (Amps)9.459.489.519.489.379.269.11
    55Capacity (w)103291296016054196552148223808
    Input (w)682568086783674267136676
    Current (Amps)10.2610.310.2910.1710.069.92

    Note:

    Rating Conditions 11.1k Superheat, 8.3K Subcooling