Condensing Unit Specifications Weight | 36 Kg |
Liquid Line Connection | 3/8 flare |
Suction Line Connection | 1/2 flare |
Total RLA | 7 Amps |
Receiver Capacity R134A | 0 Kg |
Compressor Voltage | 198-254V / 1 / 50Hz |
Motor Type | CSR |
Fan Motors Quantity | 1 |
Diameter | 300 mm |
Voltage | 220V / 1 / 50Hz 25w |

Units Dimensions (mm) |
---|
H | 340 |
W | 430 |
D | 480 |
a | 310 |
R404A Ambient (°C) | Refrigeration Capacity (w) |
---|
Evaporating Temperature (°C) |
---|
-20 | -15 | -10 | -5 | 0 | 5 |
---|
32 | 1165 | 1410 | 1665 | 1925 | 2195 | 2460 |
Note:
Capacities @ 32ºC ambient based on CECOMAF conditions: Suction Gas Temperature +32ºC, Temperature of refrigerant @ condenser outlet is subcooled within the condensing limits of the unit.
No receiver or service valves fitted.
R507 Ambient (°C) | Refrigeration Capacity (w) |
---|
Evaporating Temperature (°C) |
---|
-20 | -15 | -10 | -5 | 0 | 5 |
---|
32 | 1165 | 1410 | 1665 | 1925 | 2195 | 2460 |
Note:
Capacities @ 32ºC ambient based on CECOMAF conditions: Suction Gas Temperature +32ºC, Temperature of refrigerant @ condenser outlet is subcooled within the condensing limits of the unit.
No receiver or service valves fitted.