Enthalpy Hermetic Cond Unit- 1Ø 2HP - CS14260A1

Enthalpy Hermetic Cond Unit- 1Ø 2HP

Part Number: CS14260A1

Enthalpy Hermetic Cond Unit- 1Ø 2HP

Part Number: CS14260A1
Enthalpy

Sign in to your Aire-Biz account to view pricing and stock levels.

Sign in

Not an Airefrig customer? Complete our online account application form here to apply for a credit account.

  • Enthalpy Hermetic Flat Base Condensing Units

    Airefrig Australia’s range of Enthalpy condensing units is one of the highest quality units available for the Australian market. The condensing units have many standard fitted features, previously being options.

    The condensing units are rated to 43 ambient and are fitted with a fan speed controller. This means they can be applied in the hot climate of far North Queensland to the cooler areas of Tasmania.

    The Enthalpy condensing unit is the most complete condensing unit available saving time in installation for contractors.

    Standard Fitted Features:

    • Copeland CS Compressors with Oil Sight Glass
    • Crankcase Heater
    • Rotalock Valves
    • HP/LP Control
    • Gomax Flexible Control Hoses
    • Liquid Line Drier & Sight Glass
    • Oil Separator (Pre-charged with POE Oil)
    • Liquid Receiver
    • Galvanised Black Powder Coated Unit Base
    • Supercoat Condenser Treatment (5000 Hour Salt Spray Test)
    • ebmpapst Condenser Fans
    • Saginomiya Condenser Fan Speed Controller (Not available for CS10100A1 Units)
    • 3PH Contactor & Electronic Motor Protection Relay
    • Phase Loss & Phase Imbalance Protection
    • Pre-wired Back to Junction Box
    • 1.22mm (18G) Interconnecting Copper Pipe Work
    • Nitrogen Holding Charge

     

    Options:
    • Suction Accumulator (Not available for CS10100A1 Units)
    • Unit Weather Cover (knockdown form)

  • Condensing Unit Specifications
    Weight98 Kg
    Liquid Line Connection1/2 "
    Suction Line Connection3/4 "
    Receiver Capacity R404A4.29 Kg
    Compressor
    Nominal HP2 HP
    Max Continuous Current17.5 Amps
    Rated Load Amps12.5 Amps
    Locked Rotor Amps58 Amps
    Voltage230V / 1 / 50Hz
    Motor TypeCSR
    Crankcase Heater240/480/600v 40 w
    Fan Motors
    Total FLA0.73 Amps
    Quantity1
    Diameter400 mm
    Voltage230V / 1 / 50Hz
  • Compressor ModelCS14K6EPFJ595
    Compressor Start Relay040000160
    Compresor Run Capacitor014003711
    Compressor Start Capacitor014000851
    Oil Separator (Internal Float)EOS1004L
    Liquid Receiver1300134B
    Receiver Outlet ValveR051FA8DS
    Receiver Outlet Gasket020002800
    Suction Service ValveR052FB4DS
    Suction Valve Gasket020002802
    Unit Electrical BoxAIRENTENCL
    Liquid Line Drier / Sight Glass ComboCSG084S
    Dual Pressure ControlDNSD306X
    Condenser Fan Model (ebm)S4E400AP0244
    Fan Speed ControllerRGEZ1N45MFQ1
  • Enthalpy_Herm-A
  • CSFB&ML1PH(100214)
  • R404A
    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -30-25-20-15-10-50
    321418195126013320411549315761
    381171164822302873356242794987
    43969139919212498311437444360

    Note:

    Nominal ratings should be used as a guide, based on 18 degree Celsius return vapour and inherent liquid subcooling.
    R507
    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -30-25-20-15-10-50
    321418195126013320411549315761
    381171164822302873356242794987
    43969139919212498311437444360

    Note:

    Nominal ratings should be used as a guide, based on 18 degree Celsius return vapour and inherent liquid subcooling.
    R134A
    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-50510
    32192625513106403248785951
    38166622082979329139824858
    43144919302358287734824248

    Note:

    Nominal ratings should be used as a guide, based on 18 degree Celsius return vapour and inherent liquid subcooling.
    Fan speed controller will require to be adjusted to suit R134a refrigerant at time of commissioning
  • Notes for Commissioning:

    Set Dual Pressure Control to suit application.
    Set Fan Speed Control to suit application (ie: R134a).
    Adjust Motor Current Overload to suit application.
    Unit delivered with 1200 kpa nitrogen holding charge.
    Remove/adjust transport protection (Bitzer comps only).
    Check integrity of electrical connections/terminations.
    Check integrity of fixing screws & bolts etc.

My Comparison List