Optyma Plus Inverter Condensing Unit- 3Ø - OPMPPM035VVLP01E

Optyma Plus Inverter Condensing Unit- 3Ø

Part Number: OPMPPM035VVLP01E

Optyma Plus Inverter Condensing Unit- 3Ø

Part Number: OPMPPM035VVLP01E
Danfoss

Sign in to your Aire-Biz account to view pricing and stock levels.

Sign in

Not an Airefrig customer? Complete our online account application form here to apply for a credit account.

  • Danfoss Optyma Plus Inverter Condensing Units

    With Danfoss, you get more than reliable solutions for cold rooms. Contractor-friendly products built with market leading expertise that are tailored to suit the local ambient conditions and regulations to save on installation and maintenance. Make the right choice for optimum protection of perishables, efficient operation and long lifespan.

    Danfoss Optyma Plus Inverter Units are designed with the unique benefits of stepless inverter scroll technology resulting in a 20-30% higher energy efficiency in a flexible plug-and-play package for medium and high temperature refrigeration applications.

    Main Product Features

    Outdoor Applications

    • Weatherproof compact design housing
    • Robust and resistant to corrosion
    • Hinged access doors

    Quiet Operation

    • Acoustic dampening insulation
    • Low day/night controller operation
    • Highly optimized fan blade

    Micro Channel Condenser Coil

    • High efficiency
    • Less refrigerant charge
    • Longer life time & easy cleaning

    Optyma Plus Electronic Controller

    • Parameter monitoring & control
    • Plug & play flexible package
    • Built in clock function with power reserve
    • Compressor on/off & variable speed regulation
    • Intelligent fan speed control
    • Crankcase heater control
    • Condensing pressure control in relation to ambient
    • Monitoring discharge temperature TD
    • Oil return management at variable speed operation
    • Built-in Modbus data communication
    • High & low pressure monitoring

    Standard Features

    • Medium Temperature Units
      (R404A, R507, R449A, R448A, R407A, R407F)
    • Variable Speed Scroll Compressors
    • Compressor Drive with EMI filter
    • Acoustic Housing
    • Compressor Oil Sight Glass
    • Crankcase Heater
    • Shut Off Ball Valves
    • High Efficiency Fan Motor
    • Hi Pressure & Low Pressure Switches
    • Liquid line Drier & Sight Glass
    • Oil Separator with oil heater
    • Liquid Receiver with isolator valve
    • Circuit Breaker MCB, comp contactor & overload
    • IP54 rating for complete unit
      (Compressor: IP22 , Fan: IP54 , Controller: IP20 , Drive: IP20)
  • Condensing Unit Specifications
    Weight125 Kg
    Liquid Line Connection5/8 "
    Suction Line Connection3/4 "
    Receiver Capacity6.2 L
    Compressor
    Max Continuous Current9.8 Amps
    Voltage400V / 3 / 50Hz
    Motor TypeInverter
    Crankcase Heater240V / 1 / 50Hz 70w
    Fan Motors
    Total FLA0.96 Amps
    Quantity1
    Diameter500 mm
    Voltage230V / 1 / 50Hz
  • Compressor - Scroll Inverter120G0159
    Condenser118U3494
    Fan Assembly118U3829
    Receiver118U3476
    Filter Drier023Z5045
    Sight Glass014F0174
    Liquid Line Valve009G7053
    Suction Line Valve009G7054
    High Pressure Transmitter118U3722
    Low Pressure Transmitter118U3721
    Suction & Ambient Temperature Sensor084N0003
    Discharge Temperature Sensor084N2007
    Fan Grill118U3485
    Optyma Plus Controller118U3465
    Main Switch118U3854
    Compressor Contactor118U3847
    Door Handle118U3858
    Crankcase Heater120Z5040
    High Pressure Switch118U3718
    Low Pressure Switch118U3720
    Acoustic Hood120Z5043
    Compressor Drive CDS803 7.5kw H Optyma Invert118U3973
    EMI Filter (Drive)118U3972
    EMI Filter (Controller)118U3974
    Compressor Oil120Z0648
    Oil Separator118U3981
    Panel - Top118U5131
    Panel - Fan118U5132
    Panel - Back118U5133
    Panel - Front118U5134
    Panel - Access118U5135
    Panel - Left Side118U5165
  • danfoss_optyma_plus_inverter
  • danfoss_optyma_plus_inverter
  • R404A

    Frequency - 100

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-505
    3231583899475557356846
    3828543533431752156236
    4325903215393747665711

    Frequency - 150

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-505
    3246105659686682409790
    3841695126622674818899
    4337844662567268268133

    Frequency - 200

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-505
    325901721887271043812360
    38533165297901946011214
    43482859267183861410227

    Note:

    Performance data, based on 10K Superheat and inherent sub-cooling
    R507

    Frequency - 100

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-505
    3231583899475557356846
    3828543533431752156236
    4325903215393747665711

    Frequency - 150

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-505
    3246105659686682409790
    3841695126622674818899
    4337844662567268268133

    Frequency - 200

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-505
    325901721887271043812360
    38533165297901946011214
    43482859267183861410227

    Note:

    Performance data, based on 10K Superheat and inherent sub-cooling
    R448A

    Frequency - 100

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -10-505
    323616444253816441
    383327410249835977
    433076380646375577

    Frequency - 150

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -10-505
    325238639677139200
    384827590771368523
    434472548766417945

    Frequency - 200

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -10-505
    3266838119976511631
    3861857518904510779
    4357577006843610061

    Note:

    Performance data, based on 10K Superheat and inherent sub-cooling
    R449A

    Frequency - 100

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -10-505
    323616444253816441
    383327410249835977
    433076380646375577

    Frequency - 150

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -10-505
    325238639677139200
    384827590771368523
    434472548766417945

    Frequency - 200

    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -10-505
    3266838119976511631
    3861857518904510779
    4357577006843610061

    Note:

    Performance data, based on 10K Superheat and inherent sub-cooling
  • Information for Optyma Plus Inverter Units

    Optyma™ Plus Inverter are a perfect solution for typical MBP applications such as food retail, petrol sites & cold rooms etc.
    All units are fully wired, factory tested, have one cabinet size and are equipped with one fan.

    It is important to ensure the condensing unit capacity at minimum speed (30 rps) will not be higher than the required cooling capacity of the smallest evaporator. Failure to ensure this may be detrimental to the unit in the longer term.

    The Optyma™ Plus Inverter is equipped with a IPM (Interior Permanent Magnet) motor. The compressor should never be operated without a frequency converter as it would be destroyed immediately if connected directly to the public network.

    It is extremely important to select the correct suction line insulation thickness in order to:
    Avoid high superheat during high ambient conditions that can create high discharge temperatures.
    Avoid low superheat during low ambient conditions that can cause the refrigerant to condensate in suction line.

    Protection and features:

    Electronic thermal compressor protection against overload.
    Temperature monitoring of the heat sink ensures that the frequency converter trips in case of overtemperature.
    The frequency converter is protected against short-circuits between compressor terminals U, V, W.
    When a compressor phase is missing, the frequency converter trips and issues an alarm.
    When a mains phase is missing the frequency converter trips or issues a warning (depending on the load).
    Monitoring of the intermediate circuit voltage ensures that the frequency converter trips when the intermediate circuit voltage is too low or too high.
    The frequency converter is protected against ground faults on compressor terminals U, V, W.
    Occurring alarms will be shown in the controller display and by the red LED in front of the frequency converter.
    The root cause of an individual alarm can be shown with an optional LCP (local control panel, code 120Z0581) or the MCT10 setup software.

    Emergency running without controller:

    If the controller fails the condensing unit can be operated when the controller standard wiring (WD1) is modified to temporary wiring as described in the application guidelines. (authorized electricians only to apply any modifications)

    EMC compliance:

    All necessary actions are taken to secure EMC compliance of complete condensing unit.
    Warning - working on unit that has been switched OFF:
    Frequency converters have DC-link capacitors that remain charged even when the frequency converter is not powered.
    To avoid an electrical hazard disconnect AC mains & wait 15 min for the capacitors to fully discharge before work on unit.
    Failure to wait for the specified time to expire after power is terminated to the unit could result in serious injury or death.
    Note: Digital inputs are not a safety switch & do not disconnect the frequency converter from the mains.
    Do not remove mains connections, compressor connections or other power connections while the frequency converter is still connected to power.

    Leakage Current:

    The ground leakage current from the frequency converter exceeds 3.5 mA. According to IEC 61800- 5-1 a reinforced Protective Earth connection must be ensured with a min. 10 mm2 Cu or an additional PE wire – with the same cable cross section as the mains wiring - must be terminated separately.

    Residual Current Device:

    This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection only an RCD of Type B (time delayed) shall be used on the supply side of this product.

    Phase sequence:

    Optyma™ Plus INVERTER units are equipped with variable speed scroll compressors for which proper phase sequence is compulsory in order to secure rotation in right direction and therefore compression. The phase sequence has to be secured between the drive and compressor. (The phase sequence between network and unit drive is of no influence on the compressor rotation direction).

    Unit start up:

    The condensing unit controller is factory set for R449A (change as required – see application guide) for quick installation and start up. The compressor drive is fully managed by the condensing unit controller and therefore all parameters settings should be done only via condensing unit controller.
    It is compulsory to energize crankcase and oil separator heaters at least 1 hour before initial start-up and start-up after prolonged shutdown to remove refrigerant in liquid phase from the compressor.

    Unit maximum test pressure is 28 bar.

    Note: Please read appropriate application guidelines & manuals for more detailed information.
  • Micro Channel Heat Exchanger technology | A whole new level of system efficiency

My Comparison List

Compare Clear all
Sorry, you can only compare products from the same category.