Enthalpy TD Hermetic Cond Unit - 3Ø 2HP - TDCS14ML4003

Enthalpy TD Hermetic Cond Unit - 3Ø 2HP

Part Number: TDCS14ML4003

Enthalpy TD Hermetic Cond Unit - 3Ø 2HP

Part Number: TDCS14ML4003
Enthalpy

Sign in to your Aire-Biz account to view pricing and stock levels.

Sign in

Not an Airefrig customer? Complete our online account application form here to apply for a credit account.

  • Enthalpy Hermetic TD Series Condensing Units

    Airefrig Australia’s range of Enthalpy condensing units is one of the highest quality units available for the Australian market. The condensing units have many standard fitted features, previously being options.

    The condensing units are rated to 43 ambient and are fitted with a fan speed controller. This means they can be applied in the hot climate of far North Queensland to the cooler areas of Tasmania.

    The Enthalpy condensing unit is the most complete condensing unit available saving time in installation for contractors.

    Standard Fitted Features:

    • Weatherproof White Powder Coated Unit Casing
    • Hermetic Copeland Compressors
    • Compressor Oil Sight Glass
    • Crankcase Heater
    • Service Shut Off Valves
    • HP/LP Control
    • Gomax Flexible Control Hoses
    • Liquid Line Drier & Sight Glass
    • Oil Separator (Pre-charged with POE Oil)
    • Liquid Receiver
    • Top Discharge High Ambient Condenser
    • Supercoat Condenser Treatment (5000 Hour Salt Spray Test)
    • Space Saving Unit Design (Can be installed in a corner or back to back – not ML series)
    • ebmpapst Condenser Fans – Single Phase
    • Saginomiya Condenser Fan Speed Controller
    • 3PH Contactor & Electronic Motor Protection Relay
    • Phase Loss & Phase Imbalance Protection
    • Dust & Weatherproof Electrical Box
    • Pre-Wired Back to Electrical Box
    • 1.22mm (18G) Interconnecting Copper Pipe Work
    • Pre-Drilled ready to fit IPW series isolating switch (4 x M4 nutspots & 38mm diameter knockout for switch option)

  • Condensing Unit Specifications
    Weight110 Kg
    Liquid Line Connection1/2 "
    Suction Line Connection3/4 "
    Receiver Capacity R404A4.29 Kg
    Receiver Capacity R134A0 Kg
    Compressor
    Nominal HP2 HP
    Max Continuous Current6.6 Amps
    Rated Load Amps4.7 Amps
    Voltage380-420V / 3 / 50Hz
    Motor TypeDOL
    Crankcase Heater240-600V / 1 / 50Hz 40 w
    Fan Motors
    Total FLA0.73 Amps
    Quantity1
    Diameter400 mm
    Voltage230V / 1 / 50Hz
  • Compressor ModelCS14K6EPFJ595
    Compressor ContactorMC12B240V
    Compressor Electronic OverloadGMP223P22A
    Circuit Breaker Control CircuitPLSMD10
    Oil Separator (Internal Float)EOS1004L
    Liquid Receiver1300134B
    Receiver Outlet ValveR051FA8DS
    Receiver Outlet Gasket020002800
    Suction Service ValveR052FB4DS
    Suction Valve Gasket020002802
    Unit Electrical BoxAIRENTENCL
    Liquid Line Drier / Sight Glass ComboCSG084S
    Dual Pressure ControlDNSD306X
    Condenser Fan Model (ebm)S4E400AP0244
    Fan Speed ControllerRGEZ1N45MFQ1
    TD Case ModelML400
  • Enthalpy_TD-D
  • CSFB&ML3PH(270418)
  • R404A
    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-50
    323425424550795942
    382961366644305205
    432576321638684564

    Note:

    Nominal ratings should be used as a guide, based on 20 degree Celsius return vapour and inherent liquid subcooling.
    Nominal ratings should be used as a guide, based on 20 degree Celsius return vapour and inherent liquid subcooling.
    Note: Fan speed controller will require to be adjusted to suit R134a refrigerant at time of commissioning.
    R507
    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-50
    323425424550795942
    382961366644305205
    432576321638684564

    Note:

    Nominal ratings should be used as a guide, based on 20 degree Celsius return vapour and inherent liquid subcooling.
    Nominal ratings should be used as a guide, based on 20 degree Celsius return vapour and inherent liquid subcooling.
    Note: Fan speed controller will require to be adjusted to suit R134a refrigerant at time of commissioning.
    R134A
    Ambient (°C)Refrigeration Capacity (w)
    Evaporating Temperature (°C)
    -15-10-50510
    32198626313199392149396000
    38171722722990337241565071
    43149419932436301236444446

    Note:

    Nominal ratings should be used as a guide, based on 20 degree Celsius return vapour and inherent liquid subcooling.
    Nominal ratings should be used as a guide, based on 20 degree Celsius return vapour and inherent liquid subcooling.
    Note: Fan speed controller will require to be adjusted to suit R134a refrigerant at time of commissioning.
  • Notes for Commissioning:

    Set Dual Pressure Control to suit application.
    Set Fan Speed Control to suit application (ie: R134a).
    Adjust Motor Current Overload to suit application.
    Unit delivered with 1200 kpa nitrogen holding charge.
    Remove/adjust transport protection (Bitzer comps only).
    Check integrity of electrical connections/terminations.
    Check integrity of fixing screws & bolts etc.